Automatic burner control units IFS 258 for controlling and monitoring gas burners. The
automatic burner control unit is for intermittent operation. Further the automatic burner control units are equipped with signal contacts for operation and faults.
Our specialist courses are intended for operators of process heat systems, service personnel as well as planners and field workers.
P.O. BOX 2809
D-49018 Osnabrück
Strotheweg 1
D-49504 Lotte (Büren)
Germany
+49 541 1214-0
+49 541 1214-370
Automatic burner control units for controlling and monitoring gas burners, for intermittent operation, ionization or UV control, cut-off threshold for flame current variable, measuring sockets for uninterrupted flame current measurement, single-electrode operation possible, signal contacts for operation and faults, FM and CSA approved.
Immediate fault lock-out or restart following flame failure,
trial for ignition period: 3, 5 or 10 s, flame failure response time: 2 s,
mains voltage: 110 V AC, 115 V AC, 200 V AC or 230 V AC, for grounded or non grounded mains.