5.2.5.3.3 Ignition

The ignition process shall be initiated immediately or within a time to be specified in the instruction handbook after the conclusion of the pre-purging stage.

Where the main burner is ignited by means of a pilot burner, the gas supply to the main burner shall be shut off during the pre-purge and ignition of the pilot burner. The automatic shut-off valve(s) of the main burner shall open only when the pilot burner flame has been proved.

 

NOTE: Where air enriched with oxygen or oxygen alone is the oxidising agent for the combustion of a gas, (commonly called oxy/fuel firing), then the ignition procedures and times for such systems may require specific additional design attention to ensure the equivalent levels of safety.

 


The following chapters are printed with the permission of the DIN Deutsches Institut für Normung e.V. (German Institute for Standardization). For the implementation of the DIN Standard, the version with the most recent issue date is deemed authoritative. This is available from Beuth Verlag GmbH, Burggrafenstrasse 6, 10787 Berlin, Germany.

 