Gas inlet sections

overview

Gas pressure control and measuring train

With measurement, With pressure control, No tightness control, No SSV/RV, Not calibratable, 1 stream, 0 valves
Flowchart No.: 2.2.1.a
Standard: EN 746-2

No. Component description Standards and Docuthek Docuthek
010 Manual isolating valve, e.g. manual valve AKT
020 Filter, e.g. gas filter GFK

Our tip: at maximum flow rate, filters should show a pressure loss of no more than 10 mbar.

030-040 Pressure gauge, e.g. pressure gauge with capsule element KFM or pressure gauge with Bourdon tube RFM with pressure gauge valve DH or MH
050 Gas pressure regulator, e.g. pressure regulator for gas VGBF

Pressure regulators should be designed to be as small as possible.
Our tip: to achieve good control characteristics, the maximum pressure gradient (difference between the inlet pressure and the required outlet pressure of the regulator) should be fully utilized.

060 Gas metering equipment, e.g. flow meters DM, DE
070 Low-pressure cut-off, e.g. pressure switch for gas DG

The min. pressure switch setpoints to be adjusted depend on the installation location and the process conditions.

Our tip: pressure switches should be installed preferably with horizontal or vertical diaphragm. Ensure that no dirt or moisture can penetrate the open ventilation ports.

080 High gas pressure protection, e.g. pressure switch for gas DG

The max. pressure switch setpoints to be adjusted depend on the installation location and the process conditions.

Our tip: pressure switches should be installed preferably with horizontal or vertical diaphragm. Ensure that no dirt or moisture can penetrate the open ventilation ports.

Application

Main gas train to EN 746-2. This is a part of the gas distribution system of the industrial thermoprocessing equipment (IThE), e.g. for downstream multiple burner systems.

Function

If the main shut-off valve (010) is open, the pressure and quantity required for the IThE are controlled by the gas pressure regulator (050).Any dirt in the gas or pipe system will be removed by the filter (020) first.

The low-pressure cut-off (070) and the high gas pressure protection device (080) are part of the protective system. These compulsory safety devices are actuated separately by the process control system. In the case of insufficient or excessively high gas flow, the process control system will receive a signal and shut off the gas supply safely by closing two valves fitted in series. These valves can be part of the downstream burner system.
The quantity of gas consumed can be read off the flow meter (060). The inlet and outlet pressure will be displayed on the pressure gauges (030/040).